Configuring Power Control Units
Enabling 5250/5150/4800 Authentication 10-13
Enabling 5250/5150/4800 Authentication
After you have specified the 5250/5150/4800 Admin Name and
the 5250/5150/4800 Login Password for a POWER port, you can
enable 5250/5150/4800 authentication on the port.
X To enable 5250/5150/4800 authentication
1. Access the Asynchronous Command Mode for an
asynchronous port that is configured as a POWER port for
a 5250/5150/4800 unit.
2. Execute the power scp authentication enable
command:
Example Async7:0 >>power scp authentication enable
Configuring Power Boot Sequencing
A Power Boot Sequence is a break that is sent from the 5250/
5150/4800 to indicate that an outlet has been cold-booted. The
Power Boot Sequence Feature also causes the LX, rather than
the 5250/5150/4800, to turn on the 5250/5150/4800 outlets
from a cold boot.
The Power Boot Sequence Feature can only be enabled on a port
that is configured as a POWER port for a 5250/5150/4800 unit.
When the Power Boot Sequence Feature is enabled on such a
port, it applies to all of the outlets that are managed from
that port.
X To enable the Power Boot Sequence Feature on a port
1. Access the Asynchronous Command Mode for an
asynchronous port that is configured as a POWER port for
a 5250/5150/4800 unit.
2. Use the power boot sequence enable command to
enable the Power Boot Sequence Feature on the port:
Example Async7:0 >>power boot sequence enable
See
“Command
Mode
Descriptions”
on page 1-5
for information
about
accessing
Asynchronous
Command
Mode.