Configuring Alarming with LX-7204T/7304T Sensor Manager and LDAM
Naming Control Outputs 15-17
Example X To configure a name for a control output for
multiple controls
Use the following command syntax:
Syntax hdam control port <port_number> slot <slot_number>
point <
point_number> name <new_name>
where
L You cannot list multiple slots or points, because point
names must be unique across the Master LX Unit.
Examples
control_name_1 Specifies that the point being named is a
control output.
control_name_2 The new control name to assign to the control
output. The names must be unique across the Master
LX Unit. The name must start with a letter, and the
remainder of the name can contain only letters and/
or numbers and/or underscores.
port_number Specifies the HDAM port managing the 7204T.
slot_number Specifies a specific Slot whose point to give a new
name.
point_number Specifies a specific Point to which to give a new
name.
new_name The unique name of the control output.
Config:0 >>hdam control 3_1_8 name AuxACUnitON
Config:0 >>hdam control 5_2_31 name DoorAlarm
Config:0 >>hdam control DoorAlarm name AuxACDown
Config:0 >>hdam control port 2 slot 1 point 1 name lab1
Config:0 >>hdam control port 2 slot 4 point 8 name library