Configuring the Trigger-Action Feature
Guidelines for Creating or Modifying Actions 11-9
X To configure a humidity trigger
Execute the humidity command in the Trigger Command
Mode. The following example also includes an optional
hysteresis value of 7:
Example Trigger_HumPort4GT60:0>>humidity port 3 > 60 hysteresis 7
The hysteresis is a range that exists preceding and below the
actual threshold setting. After a threshold is crossed, any
readings within the hysteresis range are not considered a
crossing of the threshold until a measurement outside the
hysteresis has been taken. You should only configure the
hysteresis to prevent “sporadic” or “spike” humidity levels
from producing inappropriate firings of the Rule associated
with this Trigger.
X To configure a clock-based timer
An Instant Trigger is used to initiate an Action in response to
timer- or calendar-related events. A time-related event
occurs when the system clock of the LX unit reaches a
specified time. A calendar-related event occurs when the
system calendar of the LX unit reaching a specified date or
day of the week.
Execute the instant time command to specify a Time
Trigger that is based on the LX system clock reaching a
specified time of day. In the following example, the Instant
Condition is true when the LX system clock reaches 6:12 AM
each morning:
Example Trigger_SixTwelve_AM:0 >>instant time 06:12
X To configure a date-based trigger
Execute the instant date command to specify a Trigger that
is based on the LX system calendar reaching a specified date.
In the following example, the Instant Condition is true when
the LX system calendar reaches midnight (12:00 AM
00:00:01) on May 11th:
Example Trigger_MayEleventh:0 >>instant date 05/11