15-12 Configuring the Fault State for Alarm Inputs
LX Series Configuration Guide
X To configure the fault state for alarm inputs for
multiple alarms
Use the following command syntax:
Syntax hdam alarm <alarm_name> hdam alarm port <port_number>
slot [<
slot_list>|all] point [<point_list>|all]fault state
[open|closed]
where
Example
alarm_name The name of the alarm on which you want to open or
close the fault state. This entry is in the order port_slot_
alarm (e.g., 5_2_31, or BankVaultDoor). The value of
alarm_name can be a descriptive name or a default
name.
port_number Specifies the LX HDAM port managing the 7204T.
slot_list Specifies a list of Slots on whose points you want to
change the fault state. The list can contain single items,
lists (such as 1,3,4) or ranges (such as 1-4), or
combination.
point_list Specifies a list of Points on which you want to change
the fault state. The list can contain single items, lists
(such as 1,3,4) or ranges (such as 1-32), or a
combination.
all The fault state specified in this command applies
to all Slots or Points (or both) managed by this
LX Master Unit.
open The point will be in Alarm when it is open.
closed The point will be in Alarm when it is closed. This is the
default setting.
Config:0 >>hdam alarm SafedepositDoor fault state open
Config:0 >>hdam alarm 5_2_31 fault state closed
Config:0 >>hdam alarm port 2 slot 1,2 point 1,2,3,4 fault state open
Config:0 >>hdam alarm port 2 slot 1-4 point 6-18 fault state closed