Configuring Alarming with LX-7204T/7304T Sensor Manager and LDAM
Enabling and Disabling the Analog State 15-29
Examples
Enabling and Disabling the Analog State
Use the following commands to configure the state for a specific
analog input or multiple analog inputs.
X To enable and disable the analog state
Use the following command syntax:
Syntax hdam analog <analog_name> state [enable|disable]
hdam analog port <port_number> slot [<slot_list>|all]
point [<
point_list>|all] state [enable|disable]
where
Examples
all The default command will apply to all Slots or Points
(or both) managed by this LX Master Unit.
Config:0 >>hdam analog port 2 slot 1,2 point 1,2,3,4 default nam
Config:0 >>hdam analog port 2 slot 1-4 point 6-8 default name
Config:0 >>hdam analog port 2 slot all point all default name
Config:0 >>hdam analog fan_window default name
analog_name Specifies an Analog Input name. The value of analog_
name can be a descriptive name or a default name.
port_number Specifies the LX HDAM port managing the 7204T
slot_list Specifies a list of Slots on which you want to enable
the state. The list can contain single items, lists (such
as 1,3,4) or ranges (such as 1-4), or a combination.
point_list Specifies a list of Points on which you want to enable
the state. The list can contain single items, lists (such
as 1,3,4) or ranges (such as 1-8), or a combination
all
The default command will apply to all Slots or Points
(or both) managed by this LX Master Unit
Config:0 >>hdam analog port 2 slot 1,2 point 1,2,3,4 state enabl
Config:0 >>hdam analog port 2 slot 1-4 point 6-8 state enable
Config:0 >>hdam analog port 2 slot all point all state disable
Config:0 >>hdam analog fan_window state enable