11-20 Disabling Rules
LX Series Configuration Guide
6. Execute the following command at the Trigger-action:0 >>
prompt:
Example Trigger-action:0 >>rule name high-temp-off
7. Execute the following command at the Rule_high-temp-
off:0 >>
prompt:
Examples Rule_high-temp-off:0 >>trigger check4-temp
Rule_high-temp-off:0 >>action temp-ac-power-off
Rule_high-temp-off:0 >>enable
8. At the Rule_high-temp-off:0 >>prompt, type exit
three times.
9. Execute the following command at the InReach:0 >>
prompt to save your configuration:
Example InReach:0 >>save config flash
Then type:
Example InReach:0 >>show trigger-action trigger name
check4-temp
The following screen displays:
Figure 11.4 Show Trigger Action Trigger Screen
10.Type the following command at the InReach:0 >> prompt:
Example InReach:0 >>show trigger-action action name
temp-ac-power-off
The following lines are displayed:
Time: Wed, 14 Mar 2007 09:08:19 US/EASTERN
Trigger Name: check4-temp Type: Temperature (C)
Errors: 0
Port: 5
Hysteresis: - 2 Celsius
Temperature: > 25 Celsius
Time: Tue, 27 Mar 2007 09:08:19 US/EASTERN
Action Name: temp-ac-power-off
Command: outlet 11:5 off