11-18 Disabling Rules
LX Series Configuration Guide
4. Execute the action command to specify an Action
for the Rule:
Example Rule_ACTurnOnRule7:0 >>action TurnonAC7
5. Execute the enable command to enable the Rule:
Example Rule_ACTurnOnRule7:0 >>enable
When the Rule is enabled, it is put into use by the Trigger-Action
Feature; the Trigger-Action Feature executes the Action
associated with the Rule when the condition specified for the
Rule Trigger is true.
In the preceding example, the Trigger associated with the Rule
ACTurnOnRule7 is TempPort3GT34; the Action associated with
ACTurnOnRule7 is TurnonAC7.
If the Trigger condition is temperature port 3 > 34 celsius and
the Action is outlet 5:7 on, this Rule will cause outlet 5:7 to be
turned on when the temperature on SENSOR port 3 is greater
than 34 degrees Celsius.
Disabling Rules
When a Rule is disabled, it is taken out of use by the Trigger-
Action Feature; the Trigger-Action Feature does not execute the
Action associated with the Rule when the condition specified for
the Rule Trigger is true. There are two ways to disable a Rule.
X To disable a rule in Rule command mode
Execute the disable command (at the Trigger-Action Rule
level):
Example Rule_ACTurnOnRule7:0 >>disable
X To disable a rule in Trigger-Action command mode
Execute the rule command with the disable command (at
the Trigger-Action level):
Example Trigger-Action:0 >>rule name ACTurnOnRule7 disable