Configuring Alarming with LX-7204T/7304T Sensor Manager and LDAM
Using the Control Output Commands 15-47
Using the Control Output Commands
This section explains how to configure the control output
commands, including the following:
Naming Control Outputs
Configuring a Control Output Energize as Assert or
Deassert
Set Control Output Signal to Assert or Deassert
Configuring a Control Output Description String
Defaulting a Control Output Description
Resetting Control Output Name to Default Setting
Naming Control Outputs
The default name for a control output is canonically derived
from the port number and point number. For example, the
default name for the 1st control output on the LDAM
port 5 is 5_1.
You can configure by the default name (if known), or by the
physical location on the LDAM.
X To configure a descriptive name for any control output
Execute the following Privileged command:
Syntax ldam control <control_name_1> name <control_name_2>
where
Examples
control_name_1 Specifies that the point being named is a Control
Output.
control_name_2 The new control name to assign to the control
output. The names must be unique across the
Master LX Unit. The name must start with a letter,
and the remainder of the name can contain only
letters and/or numbers and/or underscores. The
limit is 31 characters.
Config:0 >>ldam control 5_1 name AuxACUnitON