Configuring Alarming with LX-7204T/7304T Sensor Manager and LDAM
Configuring an Alarm Input Description String 15-7
Configuring an Alarm Input Description String
Use the following commands configure an Alarm Description
String for a specific alarm or for multiple alarms.
X To configure an alarm input description string
1. Use the following command syntax to configure an alarm
input description string for a specific alarm:
Syntax hdam alarm <alarm_name> description <string>
2. Use the following command syntax to configure an alarm
input description string for multiple alarms:
Syntax hdam alarm port <port_number> slot [<slot_list>|all]
point [<
point_list>|all] description <string>
where
Example
alarm_name The name of the alarm on which you want to configure a
description string. This entry is in the order port_slot_
alarm (e.g., 5_2_31, or BankVaultDoor).
port_number Specifies the HDAM port managing the LX-7204T/
7204T.
slot_list Specifies a list of Slots on which you want to configure a
description string. The list can contain single items, lists
(such as 1,3,4) or ranges (such as 1-4), or a
combination.
point_list Specifies a list of Points on which to configure a
description string. The list can contain single items, lists
(such as 1,3,4) or ranges (such as 1-32), or a
combination.
all Specifies that all Slots or Points managed by the LX
Master Unit will be as specified in this command.
string
The description of the alarm input (a maximum of 63
characters long).
Config:0 >>hdam alarm 5_4_8 description lab door 1
Config:0 >>hdam alarm 3_1_8 description lab door 2
Config:0 >>hdam alarm port 2 slot 1,2 point 1-4 description lab1
Config:0 >>hdam alarm port 2 slot all point all description
library second floor