Configuring Alarming with LX-7204T/7304T Sensor Manager and LDAM
Naming Control Outputs 15-49
X To configure control output signal to assert or deassert
for a specific control
Use the following command syntax:
Syntax ldam control <control_name> set [assert|deassert]
X To configure control output signal as assert or deassert
for multiple controls
Use the following command syntax:
Syntax ldam control port <port_number> point <point_number>
set [
assert|deassert]
where
Examples
port_number Number of the LDAM port
control_name Specifies a Control Output Name. The default name for
an alarm input or control output is canonically derived
from the port number, slot number and point number.
For example, the default name for the 1st control output
being managed by LDAM port 5 is 5_1
point_number The point whose state you want to set to assert or
deassert. The only option is 1
assert|deassert Set the specified Control Output signal to
Assert|Deassert. Assert is the default setting.
Config:0 >>ldam control 5_1 set assert
Config:0 >>ldam control 3_1 set deassert
Config:0 >>ldam control port 2 point 1 set assert