
15-48 Naming Control Outputs
LX Series Configuration Guide
X To set the energize state of a named control to assert
or deassert for a specific control
Use the following command syntax:
Syntax ldam control <control_name> energize state
[
assert|deassert]
X To set the energize state of a named control to assert
or deassert for multiple controls
Use the following command syntax:
Syntax ldam control port <port_number> point <point_number>
energize state [
assert|deassert]
where
Examples
port_number The number of the LDAM port.
control_name Specifies a Control Output Name. The default name
for an alarm input or control output is canonically
derived from the port number, slot number and point
number. For example, the default name for the 1st
control output being managed by LDAM port 5 is 5_1.
point_number The point whose state you want to configure to assert
or deassert. The only option is 1.
assert|deassert Configure the specified Control Output energize state
to Assert|Deassert. Assert is the default setting.
Config:0 >>ldam control 5_1 energize state assert
Config:0 >>ldam control 3_1 energize state deassert
Config:0 >>ldam control port 2 point 1 energize state asser
Comentarios a estos manuales