Configuring Alarming with LX-7204T/7304T Sensor Manager and LDAM
Setting the Active State of a Named Control 15-21
Example
Setting the Active State of a Named Control
Use the following commands to set the active state of a named
control to open or closed, or to set the active state for a specific
control or for multiple controls to open or closed.
X To set the active state of a specific control to
open or closed
Use the following command syntax:
Syntax hdam control <control_name> active state [open|closed]
X To set the active state of multiple control outputs to
open or closed
Use the following command syntax:
Syntax hdam control port <port_number> slot [<slot_list>|all]
point [<
point_list>|all] active state [open|closed]
where
point_list Specifies a list of Points for which to configure a
description. The list can contain single items (such as
1,3,4) or ranges (such as 1-8), or a combination.
all Specifies that all Slot or control outputs managed by
the LX Master Unit will be as specified in this
command.
Config:0 >>hdam control Temp_AC default description
Config:0 >>hdam control 3_1_8 default description
Config:0 >>hdam control port 2 slot 1,2 point 1-4 default description
Config:0 >>hdam control port 2 slot all point all default description
control_name The name of the control output whose active state to set
open or closed.
port_number Specifies the HDAM port managing the 7204T.
slot_list Specifies a list of Slots whose points to configure as open
or closed. The list can contain single items, lists (such as
1,3,4) or ranges (such as 1-4), or a combination.